Notice(说明):
This controller is shipped with aninterlock jumper in place to prevent motor starting during set-up prcedure. Theinterlock jumper must be removed for the controller to operate automatically. Removejumper wire connected between field terminals #1 and #10 when set-up iscomplete. Remove this notice when finished.
控制柜设置联锁跳线防止设置时发动机启动。控制柜自动运行必须移除联锁跳线。跳线必须删除的联锁和自动控制器的操作。设置完成后移除#1 和#10端子间跳线。完成后移除本说明。
System status (系统状态):
Power available 电源指示
Alram报警
System pressure low官网系统压力低
Pump running泵运行
Deluge open雨淋打开
Remote start远程起动
Interlock on联锁
Fail to start起动失败
Motor overload电动机过载
Phase failure缺相
Phase reversal反相
Automatic shutdown disabled自动切断关闭
Overvotage过电压
Undervoltage欠电压
Electric true RMS metering (电子转速表):
Circuit breaker disconnecting means断路器切断机构
To start 起动
Cloase door and then place thecircuit breaker in the “ON” position.关闭柜门,断路器合闸
A-Pump will start if the pump pressure isbelow the pressure start setting. 泵压低于起动压力设定值时启泵。
B-For manualstart, press the “START” pushbutton.按“起动”按钮手动起动。
C-For energency start,push“energencyRUN” mechanism. 推应急运行操纵杆应急起动。
To stop 停止
Press “STOT” pushbutton.按“停止”按钮
If in energency RUN position:如果在应急运行状态
A - Place circuit breaker in the “OFF”position.断路器分闸
B - Turn “energency RUN” mechanism and release.推应急运行操纵杆然后释放
C - Place circuit breaker in the “ON”position.断路器合闸
If pump restarts, pump pressure is below thepressure start setting.在泵重新起动,泵压低于起动压力设定值。